Question
“Why will Pump 4 not start?”
Finding
LS-104 low-low is blocking the start permissive.
In the read-only sample snapshot observed 2026-08-29 14:12Z, the start request, automatic mode, emergency-stop chain, and PowerFlex-ready state are satisfied while LS_104_LLO is active. The normally closed LS_104_LLO instruction therefore evaluates false, breaking rung continuity before P104_START_PERM. This establishes the blocking condition for that snapshot only; the physical root cause (a true low-low level versus a switch, wiring, or input-channel fault) is not yet established and requires field corroboration.
Bounded hypotheses
| # | Hypothesis | Rationale |
|---|---|---|
| 1 | Process low-low interlock is legitimately active | The logic and read-only snapshot agree that LS_104_LLO is active while the rest of the start chain is satisfied. |
| 2 | Field switch, wiring, or input-channel fault | The drawing maps the signal to X2-17 and slot 4 channel 7, but no current field evidence confirms the physical state. |
| 3 | Unexpected logic or drive fault | The reviewed rung and drive export do not support either condition. |
Next approved action · authority: read-only
Verify the field state: Under the approved read-only procedure, compare the LS-104 field indication with terminal X2-17 and the slot 4 channel 7 input LED. Capture a photo in Mobile Field Check. Do not bypass the interlock.
Stop conditions, on screen at every step:
- Arc-flash boundary cannot be maintained
- Unexpected cabinet condition
- Technician lacks cell authorization
- Process safety state is unclear
Field task issued to Mobile Field Check
Compare the LS-104 field indication with terminal X2-17 and the slot 4 channel 7 input LED, exactly as found, and capture one field photo and one cabinet photo.
Cited evidence
| ID | Source | Version | Observed | State | Supporting fact |
|---|---|---|---|---|---|
| EV-R27 | Routine P104, rung 27 | L5X sample export BRPLC-PT104-V12 | — | verified | P104_START_PERM requires START_REQ, AUTO_MODE, NOT ESTOP_ACTIVE, NOT LS_104_LLO, and VFD_READY. |
| EV-SNAPSHOT | Read-only sample tag export | — | 2026-08-29T14:12Z | observed | START_REQ=true AUTO_MODE=true ESTOP_ACTIVE=false LS_104_LLO=true P104_START_PERM=false |
| EV-VFD | PowerFlex sample fault export | — | 2026-08-29T14:12Z | extracted | VFD_READY=true Active fault count=0 |
| EV-E104 | Electrical drawing E-104 | Drawing E-104 rev C | — | verified | LS-104 terminates at X2-17 and maps to slot 4 channel 7. |
Simulated review note
In the pilot workflow a controls engineer reviews this trace and the field observation on a scheduled basis before the incident closes. This sample shows the record shape; the review shown on the public site is simulated, and no engineer reviewed a real plant for this document.