Sample record — no customer data · generated from the sanitized Blue Ridge Lab fixture

Verified equipment record PT-104

Linked incident: INC-PT104-001 · Blue Ridge Lab · PT-104 Pump Skid · PT104_Lab_PLC (sample)

This is the public sample of the equipment record a pilot cell builds up over time. Every fact below is drawn from the PT-104 sample fixture; fields the fixture does not support are marked unknown, never guessed. Customer records are authenticated and tenant-isolated; this page is the sample only.

Asset identity

Asset IDPT104-PUMP-4
AssetPump 4 (PT-104 transfer pump)
RoleTransfer pump on the PT-104 skid, started through the P104_START_PERM permissive.
DrivePump 4 drive (PowerFlex VFD): Variable-frequency drive feeding Pump 4; reports VFD_READY.
Interlock deviceLS-104 low-low level switch: Low-low level interlock on the PT-104 supply tank; wired to terminal X2-17, slot 4 channel 7.

Logic revision

Loaded logicL5X sample export BRPLC-PT104-V12
Cited rungRoutine P104 · rung 27: XIC(START_REQ)XIC(AUTO_MODE)XIO(ESTOP_ACTIVE)XIO(LS_104_LLO)XIC(VFD_READY)OTE(P104_START_PERM);
Vault manifestBRPLC-PT104-V12: Known-good L5X SHA-256 verified. Controller firmware 32.014 captured.

Drawing reference & I/O mapping

DrawingDrawing E-104 rev C (Drawing E-104 page 6)
TerminationLS-104 terminates at X2-17 and maps to slot 4 channel 7.
Cable endpoints beyond documented terminationUnknown — not in sample evidence

Timestamped observations

ObservedSourceRecorded state
2026-08-29T14:12ZRead-only sample tag exportSTART_REQ=true; AUTO_MODE=true; ESTOP_ACTIVE=false; LS_104_LLO=true; P104_START_PERM=false
2026-08-29T14:12ZPowerFlex sample fault exportVFD_READY=true; Active fault count=0
2026-08-28T19:42ZLogic diff BRPLC-DIFF-014TON T4:18 preset changed from 3000 ms to 5000 ms after the last approved baseline.

Review status

Simulated review for this sample. In the pilot workflow, a controls engineer reviews the trace and the field observation on a scheduled basis before the incident closes; no engineer reviewed a real plant for this document.

Explicitly unknown

FieldStatus
Electrical test results (insulation, continuity, loop checks)Unknown — not in sample evidence
Prior fixes and maintenance history for this assetUnknown — not in sample evidence
Cable endpoints beyond the documented X2-17 terminationUnknown — not in sample evidence

Public sample link

https://blueridgeplc.com/samples/equipment-record-PT-104.html

The QR code is an identifier that opens this public sample page. It is never an access credential: customer equipment records are authenticated and tenant-isolated, and are never reachable from a printed code.